• Home
  • About Caledonian
  • News
  • Products
  • Applications
  • Technical Information Testing Authorities | Testing Equipment Manufacturers | Magazines | Organizations | Caledonian Corporater Website
  • Download
  • Sitemap
  • Contacts
  • Chinese

Caledonian Airport Cables

  • Airport Lighting Power Cables
  • Airport Series Runway Lighting Cables
  • Airport Lighting Fire Resistant Cables
  • Airport Lighting Flame Retardant Cables
  • FAS (Fire Alarm System)

  • Detector Cable
  • Fire Communication Cable
  • Sounder Cable
  • Control Cable
  • RS485 Data Cable

SACS (Security Access Control System)

  • RS485 Data Cables
  • Push Button Cables
  • Lock Cables
  • Card Reader Cables

CCTV (Closed Circuit TV)

  • Video Cables
  • RS485 Data Cables

PAS (Public Address System)

  • Loudspeaker Cables
  • RS485 Data Cables

BMS (Building Management System)

  • Digital Signal Cables
  • Analog Signal Cables
  • RS485 Data Cables
  • Temperature Control Cables

CPMS (Car Park Management System)

  • Communication Cables
  • Talk-back Cables

Baggage Handling System Cables

Caledonian Airport Cables

FAS (Fire Alarm System)

Control Cable FFX200 05SZ1-R/F 2G2.5

FFX200 05SZ1-R 2G2.5 (CU/SR/LSZH 2×2.5mmsq 300/500V class 2)

FFX200 05SZ1-F 2G2.5 (CU/SR/LSZH 2×2.5mmsq 300/500V class 5)

Fire Alarm System control cables BS 7629-1 Control Cable

APPLICATIONS

The cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. The cables are designed specially for fire alarm systems where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground.

STANDARDS

Basic design BS 7629-1
Halogen Free IEC 60754-1
No corrosive gas emission IEC 60754-2
Minimum Smoke Emission IEC 61034-1/2
Reduced Fire Propagation IEC 60332-3C / NF C 32070-2.2 (C1)
Flame Retardance IEC 60332-1 / NF C 32-070-2.1 (C2)
Fire Resistance IEC 60331 / BS 5839-1 Clause 26 2d / NF C 32070-2.3(CR1)

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5.

Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.

Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.

ELECTRICAL PROPERTIES

Dielectric test: 2000 V r.m.s. x 5’ (core/core)
Insulation resistance 300 MΩ x km (at 20°C)
Short circuit temperature 350°C

PHYSICAL AND ThERMAL PROPERTLES

Temperature range during operation (fixed state): -30°C – +90°C Temperature range during installation (mobile state): -20°C – +50°C Minimum bending radius: 8 × Overall Diameter

CONSTRUCTION PARAMETERS

FFX200 05SZ1-R 2G2.5

FFX200 05SZ1-F 2G2.5

No.of core Nominal Cross Sectional Area Number & Nominal Diameter of Strands Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Approx.Weight
  mm2 No/mm mm mm mm kg/km
2 2.5 7/0.67 0.8 1.0 9.0 105
2 2.5 50/0.25 0.8 1.0 9.0 105